Each cycle irrigates longer after a hot, dry day, and for less time after a cool, humid day.
A plant uses the water the air takes from it: this is evapotranspiration (ETR). It rises with heat and falls when the air is humid. A fixed irrigation duration therefore applies too much water in cool weather and not enough in hot spells.
ETR modulation measures air temperature and humidity with the sensor on the Aqualone trigger, and adapts the duration of each cycle to these conditions.
At the start of each cycle, the system computes the mean air temperature and humidity of the last 12 hours. For an evening irrigation, this covers the day that has just ended.
At 27 °C and 65 % humidity, the programmed duration applies unchanged (100 %). Each degree above adds 2.5 %, each humidity point above removes 0.3 %, and the other way round.
| Conditions over the last 12 hours | Applied duration | Irrigation |
|---|---|---|
| 32 °C, 50 % (hot and dry) | 117 % | 11 min 42 s |
| 30 °C, 65 % | 107.5 % | 10 min 45 s |
| 27 °C, 65 % (reference) | 100 % | 10 min |
| 24 °C, 65 % | 92.5 % | 9 min 15 s |
| 22 °C, 90 % (cool and humid) | 80 % | 8 min |
They follow the sensitivity of evapotranspiration to temperature and humidity in the FAO-56 reference method (FAO Irrigation and Drainage Paper 56): about +2 to +2.6 % per degree. The reference temperature and humidity are the conditions for which the programmed duration was set.
Values shown: default settings. Your installer can adapt them to your crop and climate (reference temperature and humidity, coefficients, bounds, length of the calculation window).